Radio channel receiver Astra ri m rpu. Rice

The radio receiver is upgraded. Receiving radio notifications from registered detectors directly and via repeaters (RTR), decoding and issuing notifications to the monitoring station through relay outputs, to two built-in indicators and to the expansion line. Operating frequency range: 433.92. Supply voltage: 10÷15V. Consumption current: 65mA (in receive mode), 80mA (in transmit mode). Maximum switched voltage by relay contacts: 100V, 0.1A. Operating temperature range: -10...+50°С. Degree of protection: IP41.

Basic data

  • RPU Astra-RI-M with new software version RIM-RPU-dv10_7 on the hardware platform "dv";
  • The RPU provides operation with all detectors of the system:
    • Astra-3221 - alarm button,
    • Astra-3321 - magnetic contact detector,
    • Astra-3531 - position change detector,
    • Astra-361 isp.RK - emergency detector of water leakage,
    • Astra-421 isp.RK - detector fire smoke,
    • Astra-421 isp.RK2 - fire smoke detector with two-way communication,
    • Astra-4511 - manual fire detector,
    • Astra-4511 isp.RK2 - manual fire detector with two-way communication,
    • Astra-5121 - an IR detector with a volumetric detection zone that does not respond to the movement of animals weighing up to 20 kg,
    • Astra-5131 isp. A - IR detector with a volumetric detection zone,
    • Astra-5131 isp. B - IR detector with a surface detection zone,
    • Astra-6131 - sound detector,
    • RPDC Astra-RI-M - remote control + panic button,
    • RPD Astra-RI - a radio transmitter of the Astra-RI system in the mode of a security detector (RPDO) or fire detector (RPDP) of the Astra-RI-M system type;
  • the upgraded RPU ensures joint operation during information exchange via the expansion line with the control panel Astra-812 together with the previously issued RPU Astra-RI-M;
  • The RPU provides 3 modes of operation, set by jumpers: autonomous, extended and repeater mode (RTR), and relay and alert module (MPO) mode, installed from a computer by the Pсonf-R program (operation is supported only when working with the RPU in the extended operating mode);
  • autonomous mode work provides:
    - control by one RPU (without the use of control panel Astra-812) - up to 48 radio devices (detectors, RTR);
    - support for up to 4 RTR with one relay level;
    - programming of 2 relay outputs and 1 open collector type output using the Pсonf-R computer program,
    - the leading mode of operation of the RPU in the expansion line in relation to the Astra-821/822 relay modules, the Astra-861 display module,
    - data exchange rate on the extension line - 4800 bps,
    - changing the frequency letter of the RPU using a jumper and a button on the RPU board,
    - adjustment of the communication channel control time: 10, 20, 40 minutes or without control,
    - registration of detectors using the button on the RPU board,
    - control of prohibition/permission of output to internal relays of all types of notifications except "Alarm/Fire", "Opening RPU" and "Blocking of the radio channel",
    - activation of the "Alarm memory" mode from the key fob RPDC,
    - switching on the "Faulty circuit bypass" mode,
    - generation of a code in the Touch memory (ТМ) format for controlling arming/disarming or operation of the TM output in switch mode (armed/disarmed),
    - formation of a unique TM code for each control button of the RPDC key fob;
  • extended mode work provides:
    - connection of up to 4 remote control units to the control panel Astra-812,
    - slave (passive) mode of operation in the expansion line in relation to the control panel Astra-812. The control panel in this case is the master (master) device in relation to the RPU, Astra-821/822 relay modules, Astra-861 display module, Astra-881/882 communicators, Astra-RI RPD transmitter
    - software adjustment of the radio channel control time: from 10 to 40 minutes in increments of 1 minute or without control,
    - changing the frequency letter of the RPU from the keyboard of the Astra-812 control panel;
  • mode repeater provides:
    - transmission of notifications from the detectors registered in it (up to 47 pcs.) to the RPU,
    - changing the frequency letter using the button on the Astra-RI-M RPU board,
    - quality control of RTR communication with RPU by indication using jumper F8 on the RTR board,
    - support for 2 functions in one device: RTR and MPO. Support for the MPO function is enabled through the Astra-812 control panel menu;
  • relay and alert module mode supported only if Astra-812 control panel is available in the system and provides:
    - receiving notifications about the state of the system via radio channel from the RPU,
    - programming of 2 relay outputs and 1 open collector type output using the Pсonf-R computer program,
    - automatic adjustment of the radio channel monitoring time,
    - changing the frequency letter using the button on the Astra-RI-M RPU board;
  • relay operation tactics RPU in factory settings the same for standalone, extended operation and repeater modes:
    - relay 1 displays the status of all registered radio channel detectors of the security type (except for the key fob),
    - relay 2 displays the status of all registered fire type radio channel detectors and key fob,
    - "open collector" type output displays the status of all registered radio channel detectors in the "sound" operating mode;
  • in RPU it is provided with the help of jumpers:
    - selection of the RPU operation mode: autonomous, extended, RTR operation mode,
    - switching on the PC mode;
  • the RPU provides the ability to update the software and configure the outputs by the user from a PC using a PC program Pconf-R;
  • the RPU provides the ability to save to the PC and restore from the PC backup copies of the registration memory of radio devices in the RPU and RTR (software for PC Pconf-R);
  • connection to a PC is provided by an AM/BM type USB cable;
  • does not require obtaining permits for use from the authorities of the state radio frequency service.

Receiving radio notifications from registered detectors directly and via repeaters (RTR), decoding and issuing notifications to the monitoring station through relay outputs, to two built-in indicators and to the expansion line.

Basic data

  • RPU Astra-RI-M with new software version RIM-RPU-dv10_7 on the hardware platform "dv";
  • The RPU provides operation with all detectors of the system:
    • Astra-3221 - panic button,
    • Astra-3321 - magnetic contact detector,
    • Astra-3531 - position change detector,
    • Astra-361 isp.RK - emergency detector of water leakage,
    • Astra-421 isp.RK - fire smoke detector,
    • Astra-421 isp.RK2 - fire smoke detector with two-way communication,
    • Astra-4511 - manual fire detector,
    • Astra-4511 isp.RK2 - manual fire detector with two-way communication,
    • Astra-5121 - an IR detector with a volumetric detection zone that does not respond to the movement of animals weighing up to 20 kg,
    • Astra-5131 isp. A - IR detector with a volumetric detection zone,
    • Astra-5131 isp. B - IR detector with a surface detection zone,
    • Astra-6131 - sound detector,
    • RPDC Astra-RI-M - remote control + panic button,
    • RPD Astra-RI - a radio transmitter of the Astra-RI system in the mode of a security detector (RPDO) or fire detector (RPDP) of the Astra-RI-M system type;
  • the upgraded RPU ensures joint operation during information exchange via the expansion line with the control panel Astra-812 together with the previously issued RPU Astra-RI-M;
  • The RPU provides 3 modes of operation, set by jumpers: autonomous, extended and repeater mode (RTR), and relay and alert module (MPO) mode, installed from a computer by the Pсonf-R program (operation is supported only when working with the RPU in the extended operating mode);
  • autonomous mode work provides:
    - control by one RPU (without the use of control panel Astra-812) - up to 48 radio devices (detectors, RTR);
    - support for up to 4 RTR with one relay level;
    - programming of 2 relay outputs and 1 open collector type output using the Pсonf-R computer program,
    - the leading mode of operation of the RPU in the expansion line in relation to the Astra-821/822 relay modules, the Astra-861 display module,
    - data exchange rate on the extension line - 4800 bps,
    - changing the frequency letter of the RPU using a jumper and a button on the RPU board,
    - adjustment of the communication channel control time: 10, 20, 40 minutes or without control,
    - registration of detectors using the button on the RPU board,
    - control of prohibition/permission of output to internal relays of all types of notifications except "Alarm/Fire", "Opening RPU" and "Blocking of the radio channel",
    - activation of the "Alarm memory" mode from the key fob RPDC,
    - switching on the "Faulty circuit bypass" mode,
    - generation of a code in the Touch memory (ТМ) format for controlling arming/disarming or operation of the TM output in switch mode (armed/disarmed),
    - formation of a unique TM code for each control button of the RPDC key fob;
  • extended mode work provides:
    - connection of up to 4 remote control units to the control panel Astra-812,
    - slave (passive) mode of operation in the expansion line in relation to the control panel Astra-812. The control panel in this case is the master (master) device in relation to the RPU, Astra-821/822 relay modules, Astra-861 display module, Astra-881/882 communicators, Astra-RI RPD transmitter
    - software adjustment of the radio channel control time: from 10 to 40 minutes in increments of 1 minute or without control,
    - changing the frequency letter of the RPU from the keyboard of the Astra-812 control panel;
  • mode repeater provides:
    - transmission of notifications from the detectors registered in it (up to 47 pcs.) to the RPU,
    - changing the frequency letter using the button on the Astra-RI-M RPU board,
    - quality control of RTR communication with RPU by indication using jumper F8 on the RTR board,
    - support for 2 functions in one device: RTR and MPO. Support for the MPO function is enabled through the Astra-812 control panel menu;
  • relay and alert module mode supported only if Astra-812 control panel is available in the system and provides:
    - receiving notifications about the state of the system via radio channel from the RPU,
    - programming of 2 relay outputs and 1 open collector type output using the Pсonf-R computer program,
    - automatic adjustment of the radio channel monitoring time,
    - changing the frequency letter using the button on the Astra-RI-M RPU board;
  • relay operation tactics RPU in factory settings the same for standalone, extended operation and repeater modes:
    - relay 1 displays the status of all registered radio channel detectors of the security type (except for the key fob),
    - relay 2 displays the status of all registered fire type radio channel detectors and key fob,
    - "open collector" type output displays the status of all registered radio channel detectors in the "sound" operating mode;
  • in RPU it is provided with the help of jumpers:
    - selection of the RPU operation mode: autonomous, extended, RTR operation mode,
    - switching on the PC mode;
  • the RPU provides the ability to update the software and configure the outputs by the user from a PC using a PC program Pconf-R;
  • the RPU provides the ability to save to the PC and restore from the PC backup copies of the registration memory of radio devices in the RPU and RTR (software for PC Pconf-R);
  • connection to a PC is provided by an AM/BM type USB cable;
  • does not require obtaining permits for use from the authorities of the state radio frequency service.

Technical data

informative

  • two LED indicators:
    - red - notification indication,
    - green - indication of the presence of interference, radio congestion;
  • NEW: two programmable relay output;
  • NEW: programmable output of "open collector" type;
  • output for connection to Touch memory line;
  • expansion line input/output;
  • antenna connector;
  • USB connector.

Purpose Astra-RI-M RPU

Receiving radio notifications from registered detectors directly and via repeaters (RTR), decoding and issuing notifications to the monitoring station through relay outputs, to two built-in indicators and to the expansion line.

Basic data Astra-RI-M RPU

Astra-RI-M RPU with new software version RIM-RPU-dv10_7 on "dv" hardware platform;

Astra-RI-M RPU ensures operation with all detectors of the system:

Data exchange rate on the extension line - 4800 bps,

Changing the frequency letter of the RPU using a jumper and a button on the RPU board,

Communication channel control time adjustment: 10, 20, 40 minutes or no control,

Registration of detectors using the button on the RPU board,

Management of prohibition/permission of output to internal relays of all types of notifications except "Alarm/Fire", "Opening the RPU" and "Blocking the radio channel",

Activation of the "Alarm memory" mode from the RPDC key fob,

Enabling the Faulty Circuit Bypass mode,

Generation of a code in the Touch memory (ТМ) format to control arming/disarming or operation of the TM output in switch mode (armed/disarmed),

Formation of a unique TM code for each control button of the RPDC key fob;

extended mode provides:

Connecting up to 4 remote control units to the control panel Astra-812 or up to 3 RPU to Astra-812M with built-in RPP module Astra-RI-M,

Slave (passive) mode of operation in the expansion line in relation to the control panel Astra-812 / Astra-812M. The control panel in this case is the master (master) device in relation to the RPU, relay modules / , display module Astra-861, Astra-881/882 communicators, transmitter

Software adjustment of the radio channel control time: from 10 to 40 minutes in 1-minute increments or without control,

Changing the frequency letter of the RPU from the keyboard of the control panel Astra-812/812M;

repeater mode provides:

Transfer of notices from the detectors registered in it (up to 47 pcs.) to the RPU or to RPP Astra-RI-M,

RPU Astra-RI-M,

Quality control of RTR communication with RPU by indication using jumper F8 on the RTR board,

Support for 2 functions in one device: RTR and MPO. Support for the MRO function is enabled through the control panel menu Astra-812 or Astra-812M;

the relay and notification module mode is supported only if there is a control panel in the system Astra-812 or Astra-812M and provides:

Reception of notifications about the state of the system via radio channel from the RPU,

Programming of 2 relay outputs and 1 “open collector” type output using the Pсonf-R computer program,

Automatic adjustment of the radio channel monitoring time,

Changing the frequency letter using the button on the board RPU Astra-RI-M;

The tactics of the RPU relay operation in the factory settings is the same for the standalone, extended operation mode and the repeater mode:

Relay 1 displays the status of all registered radio channel detectors of the security type (except for the key fob),

Relay 2 displays the status of all registered fire type radio channel detectors and key fob,

The output of the "open collector" type displays the status of all registered radio channel detectors in the "sound" operating mode;

in Astra-RI-M RPU provided with jumpers:

RPU operation mode selection: autonomous, advanced, PTP operation mode,

Enabling PC mode;

in Astra-RI-M RPU it is possible to update the software and configure the outputs by the user from a PC using the Pсonf-R PC program;

in Astra-RI-M RPU the possibility of saving to a PC and restoring from a PC backup copies of the registration memory of radio devices in the RPU and RTR is provided (PC program Pсonf-R);

connection to a PC is provided by an AM/BM type USB cable;

does not require obtaining permits for use from the authorities of the state radio frequency service.

Technical data Astra-RI-M RPU

1.Working frequencies Astra-RI-M RPU:

- letter 1 - 433.42 MHz

- letter 2 - 433.92 MHz

-letter 3 - 434.42 MHz

3.Current consumption Astra-RI-M RPU in receive mode, no more than - 65 mA

4.Current consumption Astra-RI-M RPU in transmission mode, no more than - 80 mA

5. Time of technical readiness Astra-RI-M RPU, no more than - 5 s

6.Maximum voltage switched by relay contacts Astra-RI-M RPU at load current 0.1 A - 100 V

7.Maximum constant load voltage of the open collector output at a load current of 1.5 A - 24 V

8.Dash line extension length Astra-RI-M RPU(at R<100 Ом C< 0,033 мкФ) - 200 м

9. Operating conditions Astra-RI-M RPU:

Temperature - from -10 to +50°С

Relative air humidity without moisture condensation - up to 95% at +35°С

10.Astra-RI-M RPU degree of protection by the shell - IP41

11. Informative Astra-RI-M RPU

two LED indicators:

Red - notification indication,

Green - indication of the presence of interference, radio congestion;

NEW: two programmable relay outputs;

NEW: programmable open collector output;

output for connection to Touch memory line;

expansion line input/output;

antenna connector;

Peripheral repeater RO19-64-1, radio channel receiver with new software, isp. 1-3 characters, registration of up to 192 compatible wireless detectors and control panels, 3 modes of operation - standalone, relay, extended relay via PC

Purpose of the device


Video. Example of RPU Astra-RI-M in repeater mode
  • The device is required for receiving radio notifications from registered detectors, directly and through repeaters, decoding and issuing notifications to remote security.
  • Organization of wireless fire and security and other types of alarms (alarm, emergency, etc.), using addressable radio channel detectors.
  • Scope - apartment, cottage, residential building with outbuildings, office space, museum, shopping pavilions, etc.

Principle of operation

The RPU receives notifications over the radio channel, decodes them and outputs them to 2 built-in LED indicators, two alarm relays, an open collector output, as well as to a two-wire extension line.
The radio channel receiver registers up to 48 radio detectors and up to 4 repeaters offline.
In the extended mode of operation of the relay and warning module, the device receives up to 192 radio sensors, up to 4 repeaters (in any operating mode).


Video. An example of RPU Astra-RI-M in offline mode

Peculiarities


Video. An example of connecting the RPU Astra-RI-M in the extended PC mode (MRO)

Advantages of Astra-RI-M RPU

  • The device has been upgraded and runs under the new software, which ensures compatibility with previously released models.
  • A wide range of compatible multifunctional control panels and detectors - panic buttons, magnetic contact reed switches, position change sensors (IR with volumetric and surface detection zone, animal protection), water leakage alarms, fire (smoke, manual, sound) annunciators, remote control key fobs, etc. .d.
  • 3 operating modes set by jumpers (standalone, extended/repeater), and a relay/alarm module (MPO) mode set from the computer by the program.

Reliability and efficiency

Warranty period - 5 years 6 months from the date of manufacture. Astra-RI-M RPU relays for radio-controlled alarms are certified, have the permission of the State Commission for Radio Frequencies of the State Committee for Radio Frequencies, comply with the EI 1 standards in accordance with GOST R 50009-2000 and are supplied with a guarantee from the Teko manufacturer, which has proven itself well in the Russian security equipment market.

Device Specifications

ParameterMeaning
Operating frequencies433.42 MHz (letter 1), 433.92 MHz (letter 2), 434.42 MHz (letter 3)
Voltage10?15 V, max. switching voltage 100 V (relay contacts at 0.1 A), max. fast. voltage 24 V (output "open collector" at 1.5 A)
Consumption currentup to 65 mA (in receive mode), 80 mA (in transmit mode)
Extension line lengthLIN, up to 200 m (at R
Rangeup to 2500 m (no interference)
Alertgreen/red indicator light, 2 relay terminals RELAY 1/RELAY 2, OC (open collector) terminal, TM key line output, USB
Technical readiness timeup to 5 sec
Dimensions121? 79? 31 mm
Weight100 g
Temperaturefrom -10 to +50°С, at humidity up to 95% at +35°С without moisture condensation
Sheath protection degreeIP41

Symbol: NGKB.464339.005 Р019-64-1 RPU Astra-RI-M (lit.1/2/3)

Instructions

Wiring diagram - installation, installation



Rice. Schematic diagram of connecting the base to the actuators

DIY installation. Remove cover, conn. power supply 12 V, check the indication (green light) and the radio frequency letter (lit.1, lit.2, lit.3). Off power, clear memory. Use separate instructions for connecting each transmitting, relaying and receiving device (included in the delivery). The recommended placement height is 2 m. The required distance is 1 m from the sources of the force field. The signal quality is checked using the device (green indicator is on).
Professional installation. We recommend ordering the installation of a security and fire system for a summer residence, a house, an apartment, an office, a warehouse, a bank on the website of our store Grion LLC wireless alarms. Persons who have studied the operation manual and are qualified as an electrician of a fire and security alarm are allowed to work on the installation, installation, maintenance and operation of the RPU. The specialists of our company will help you choose and install the necessary sensors, key fobs, buttons, GSM controllers and console security using radio alarms.

Check the prices in our shop - we've lowered them by both blades!

Types of radio channel equipment presented on our website

  • radio sets (radio units)
  • GSM key fobs, buttons, bracelets, remotes
  • alarms (security, fire)
  • light and sound indication devices (power supplies)
  • radio sensors (ultrasonic, optical)
  • emergency wireless signaling devices (gas leaks, water leaks)

Ask managers!

Recommended for connection to the Astra-RI-M system: GSM modules, alarm control panels, alarm buttons, fire detectors, position changes, IR motion sensors, sound annunciators. If they are not available online, contact our managers to get a profitable offer - the prices in our store of wireless gsm alarms for home and summer cottages are wholesale!

Reception via radio of notifications from registered RAPs and panic buttons, decoding and issuance of notifications to two alarm relays, as well as to a two-wire extension line.

Peculiarities
control by one RPU of up to 24 RPDs and/or RPDC key fobs, Astra-3221 detectors of the Astra-RI-M system;
communication control algorithm with the issuance of appropriate notifications in case of loss of communication:
- with one RPD - through an adjustable time interval of 10/20/40 minutes, without control,
- with all RPDs - after 2 minutes;
algorithm for eliminating signal overlaps from several RPDs;
the ability to change the software in the RPU to work in any of the Astra-RI or Astra-RI-M systems;
support for the Astra-3221 detector from the Astra-RI-M system;
use of remote antennas;
RPU does not generate TM format code;
RPU does not have the ability to arm / disarm

Basic data
support for RPDC key fobs and Astra-3221 detectors of the Astra-RI-M system as a "panic button";
the system provides:
- autonomous mode of RPU. The RPU is the master (main) device in relation to the Astra-821/822 relay modules, the Astra-861 display module connected via the expansion line;
- extended RPU operation mode. Up to 4 remote control units are connected to the control panel Astra-812. The RPU is a slave (passive) device in relation to the control panel Astra-812. PPKOP Astra-812 in this case is the leading (master) device in relation to the RPU and additional equipment;
RPU provides:
- adjustment of the communication channel control time: 10/20/40 minutes, without control,
- switching on the relay opening delay - 30 seconds,
- the ability to prohibit / allow the output to the relay of all types of notifications except for "Alarm", "Opening the RPU" and "Blocking the radio channel".
RPU relay operation tactics:
- relay 1 displays the status of all registered RPDs according to the "RCN relay" tactics (closed when all registered RPDs and / or devices connected to the RPD are in the "Normal" state and armed, open when "Alarm", including from the key fob RPDC and detector Astra-3221),
- relay 2 displays the status of all registered RPDs according to the "24-hour security" tactics (always closed in the absence of alarm notifications);
does not require obtaining permits for use from the authorities of the state radio frequency service.

Technical data

Operating frequencies:
- letter 3 434.42 MHz
supply voltage 10÷15 V
current consumption 45 mA
technical readiness time 5 s
length of device extension line (at R Operating conditions:
- temperature from -10 to +50°С
- relative air humidity without moisture condensation up to 95% at +35°С
- degree of protection by the shell IP41
informative

two LED indicators:
- red - notification indication,
- green - indication of the presence of interference, radio congestion;
two relay outputs;
expansion line input/output;
antenna connector.
Attention!

Since November 2006 Astra-RI RPUs have been produced with software (SW) version RI-RPU-cv8_x.
Since November 2006, Astra-RI RPDs have been issued with software (software) version RI-RPD-cv6_x.
The updated RPU and RPD are compatible with previously produced devices of “version 02” provided that they are reprogrammed:

to ensure the operability of the previously released Astra-RI RPD version 02 with the updated Astra-RI RPU, it is necessary to change the software in the RPU to the version RI-RPU-av8_x;
To ensure the operability of the updated Astra-RI RPDs with the previously released Astra-RI RPD version 02, it is necessary to change the software in the RPD to the RI-RPD-av6_x version.